VCDM – Volume Control Damper suitable for use in high temperature applications. Damper construction is based on the SEDS-L damper which is fully tested acc. to EN 1366-10 with classification E600 120 (Ve i<->o) S 1500 Cmod MA Single, however for a volume control function the operation is manual control only.
Characteristics
- Square dampers from 200 × 200 mm to 1200 x 1200 mm
- Tested in accordance with EN 1366-1
- Mechanical handle with extended spindle to set position of the blades
- External Casing leakage class B, Internal leakage class 3 acc. to EN 1751
- For installation in vertical or horizontal position of blade
- Max. air speed in the system of 12 m/s, allowed pressure up to 500 Pa, or underpressure up to - 1500 Pa